21
Dran-View 6 User Guide
Event Types The Event List displays icons for different kinds of triggered events.
Icon Event Type
Misc. waveform events
Sag (Low threshold crossed downwards)
Sag end (Low threshold crossed upwards)
Swell (High threshold crossed upwards)
Swell end (High threshold crossed downwards)
Swell-to-Sag (High and Low thresholds crossed downwards)
Sag-to-Swell (Low and High thresholds crossed upwards)
Swell-to-Severe Swell (High-High thresholds crossed upwards)
Severe Swell-to-Swell (High-High thresholds crossed downwards)
Sag-to-Interruption (Low-Low thresholds crossed downwards)
Interruption-to-Sag (Low-Low thresholds crossed upwards)
Interruption (Low and Low-Low thresholds crossed downwards)
Interruption end (Low-Low and Low thresholds crossed upwards)
Swell-to-Interruption (High, Low and Low-Low thresholds crossed
downwards)
Interruption-to-Swell (Low-Low, Low and High thresholds crossed
upwards)
Transient
Crest limit crossed
Unknown event
/ Aggregate (multi-phase) event of any type
Sags, Swells and Interruptions are usually further subdivided by duration
(Instantaneous (0.5 - 30 cycles according to IEEE 1159), Momentary (0.5 s/30
cycles depending on disturbance - 3 s according to IEEE 1159), Temporary (3 s -
1 min according to IEEE 1159), and Sustained (more than 1 min according to
IEEE 1159)). Transients may be subdivided (examples are taken from
PowerXplorer) by direction (Upstream or Downstream), severity (Mild,
Moderate, Severe), duration (Impulsive, Notch, Multiple Notch, 1/8 Cycle,
Multiple 1/8 Cycle, 1/4 Cycle, Multiple 1/4 Cycle, Half Cycle, Full Cycle), or
type (Unipolar, Bipolar, Oscillating, Arcing, Multiple Z Crossings, Notching,
Dropout, Switch On, Switch Off, Phase Shift, DC, Capswitch, Flat Top, Peak
Limit, Amplitude Change or Miscellaneous). Other event types may have other
subdivisions.
Continued on the next page