Vista de página 43
DB-PX5 - PowerVisa 440® / PowerGuide® 4400 / PowerXplorer® PX5 Op. Skills
© 2006-2010 by PowerCET Corporation. All rights reserved. (100616)
43
©2006-2008 PowerCET Corporation. All rights reserved.
85
•The unit is now ready to
begin monitoring and to
record data in the memory
card
•Press: Next to accept
defaults, or press to modify:
•Transient Limit
•RMS Variation Limit
•Waveform Capture
•Characterizer options
•Journal Limit
•Journal Interval
Wizard Setup: Advanced Options
©2006-2008 PowerCET Corporation. All rights reserved.
86
•From the Advanced options screen,
Press: Transient Limit
•If applicable, Press: Group A B C to
simplify setup
•Press the limit field and enter the
instantaneous limit. This value is
compared against the absolute
value of each of 256 samples of
the V and I channel waveforms
•Vpk must be set higher than the
peak of the normal waveform (1.414
x the rms value) or continuous
triggering will result
•Press: Enable
•Press Amps to toggle between volts
and amps
•Press the other tabs to set other
channels
•Press: Next to continue
Wizard Setup: Transient Limits-Instantaneous Peak